POWER TRANSFORMER


POWER TRANSFORMER


Specifications to be referred:

Sl. No.

Standards

Topic

1

IS-335-1972

Specification    for    New    insulating 

   oil    for transformer and switch gear

2

IS-2026 (Part-1)-1977

Specification for power transformers-General

3

IS-2026 (part-2)-1977

Specification  for power transformers- Temperature rise

4

IS-2026(part-3)-1977

Specification for power transformers-Insulation levels

 and dielectric tests

5

IS-2026 (part-4)-1977

Specification for power transformers-Terminal markings & 

Tapping connections

6

IS-2026 (part-5)-1977

Specification for power transformers- Bushings

7

IEC:60-1973

High voltage test techniques

8

IEC:71-1976

Part  1,Part  2

Insulation coordination Terms, definitions, 

principles and rules. Application guide.

9

IS-3639

Fitting & accessories for Transformers


  Principles of  Power Transformer:

  •  Transformers are Static piece of Electrical equipment Transferring Power from one winding at one voltage to another winding at another voltage.
  • The Transformer is one of the most efficient machines with 95% efficiency, generally in lower capacities while even 99% efficiency is also achievable in higher ranges. 
  • The fundamental principle on which the Transformer works is the Electromagnetic Induction (self and mutual). 
  • Physically, a winding called Secondary is wound around a Magnetic core and over that another winding called Primary is wound round.
  • Application of an Alternating voltage V1 to the primary winding results in flow of a current and production of a self induced emf (or Counter emf) whose direction is in opposition to the one producing it. 
  • The flow of current in the Primary produces a magnetic flux which links the secondary winding and results in the production of a secondary emf called mutually induced emf. 
  • This emf is in phase opposition to the primary applied voltage V1 and its magnitude depends upon the rate of change of flux and the secondary number of turns. 
  • It can be seen that the more the primary and secondary circuits are linked together, the more direct is the exchange of energy between them. 
  • Thus when the Transformer is on No Load, the current drawn by the primary is expended to meet the Iron Losses in the core (Hysterisis and Eddy Current Losses). 
  • In fact, the No Load Current which is the resultant of the active current and the magnetizing current actually lags behind the applied Voltage at an angle less than 90 degrees. 
  • It can be seen that E1 = 4.44 * f * N1 * Bmax * A and E2 = 4.44 * f * N2 * Bmax * A from which it can be derived that V2 / V1 = N2 /N1 = E2 / E1 = K. If K > 1, the Transformer is a Step up Transformer and if K < 1 it is a Step down Transformer. 
  • It can also be shown when a Load is connected to the Transformer secondary, that on account of the Load, a separate loss of energy occurs and that the No Load Loss is independent of the Load Loss ( it is called the Fixed Loss) where as the Load Loss is a Variable Loss. 
  • The ideal condition for maximum efficiency of a Transformer is worked out to be when the No Load Losses equal the Load Losses


Types of transformers
    Transformers are largely divided into Power and Distribution Transformers and Step up or step down Transformers. Depending upon utility, the following other types of classification is also in use:

  • Generator Transformer
  • Unit Auxiliary Transformer
  • Station Transformer
  • Transmission Sub-Station Transformers
  • Auto Transformers
  • HVDC Converter Transformer
  • Arc Furnace Transformers
  • Traction Transformers
  • Earthing Transformer or the Zig-Zag
  • Generator Neutral earthing Transformer
  • Series and Shunt Reactors (strictly not a transformer) 

Constructional features of a transformer:

                 About 70% of the material used is

(1) Core (2) Winding (3) Insulating Oil Others are : (1) Structural Steel (2) Electrical grade paper such as kraft/crepe paper, (3) Press Board (4) Wood and laminated wood (5) Paper covered conductor / PVC cable (6) Insulating tapes such as cotton/Glass woven/ Polyester resin (7) Gaskets such as Neoprene/ Nitrile Rubber/Synthetic Rubber (8) Low Loss CRGO (H1B-0.23, H1B-0.27, Laser Grade ZDMH-0.23, Amorphous Metal core (9) Copper (high conductivity, sheet, strip, foil, rod, tube, tinned, flexible, braided, flat, and insulated conductors (10) Aluminum conductors-insulated, plates, alloys etc.

Core:
Core

Transformer Core


  • Core provides a high permeability closed path for Flux. It supports the winding. 
  • It consists of laminated sheet steel (CRGO or Amorphous).
  • The vertical member of the core is called the Limb /Leg and the Horizontal member of the core is called the Yoke. 
  • Core plates or laminations are very thin and coated with insulating varnish. 
  • There are two types of construction of the core viz; Core Type and Shell type. Generally in India, Core type of construction with Two/Three/Five limbed cores is used. 
  • Generally five limbed cores are used where the dimensions of the Transformer is to be limited due to Transportation difficulties. 
  • In three limbed core the cross section of the Limb and the Yoke are the same where as in five Limbed cores, the cross section of the Yoke and the Flux return path Limbs are very less (58% and 45% of the principal Limb). 
  • Shell type of construction of the core is widely used in USA. In the construction of the core the laminations of the Limb and Yoke are interleaved. 
  • The joint where these laminations meet could be Butt or Mitered. In CRGO, the Mitered Joint is preferred as it reduces the Reluctance of the Flux path and reduces the No Load Losses and the No Load current (by about 12% & 25% respectively).
  • The Limb and the Yoke are made of a number of Laminations in Steps. Each step comprises of some number of laminations of equal width. The width of the central strip is Maximum and that at the circumference is Minimum. 
  • The cross section of the Yoke and the Limb are nearly circular. Mitered joint could be at 35/45/55 degrees but the 45 one reduces wastage.
  •  The assembled core has to be clamped tightly not only to provide a rigid mechanical structure but also required magnetic characteristic. 
  • Top and Bottom Yokes are clamped by steel sections using Yoke Studs. These studs do not pass through the core but held between steel sections. 
  • Of late Fiber Glass Band tapes are wound round the Limbs tightly up to the desired tension and heat treated. 
  • These laminations, due to elongation and contraction lead to magnetostriction, generally called Humming which can be reduced by using higher silicon content in steel but this makes the laminations become very brittle.

Types of Windings:
Windings
(1)   Distributed: Used for HV windings of small Distribution Transformers where the current does not exceed 20 amps using circular cross section conductor.
(2) Spiral: Used up to 33 kV for low currents using strip conductor. Wound closely on Bakelite or press board cylinders generally without cooling ducts. However, multi layer windings are provided with cooling ducts between layers. No Transposition is necessary.
(3)    Helical: Used for Low Voltage and high currents .The turns comprising of a number of conductors are wound axially. Could be single, double or multi layer winding. Since each conductor is not of the same length, does not embrace the same flux and of different impedances, and hence circulating currents, the winding is transposed.
(4)  Continuous Disc: Used for 33kv and 132 kv for medium currents. The coil comprises of a number of sections axially. Cooling ducts are provided between each section. 
(5)  Interleaved Disc: used for voltages above 145 kV . Interleaving enables the winding withstand higher impulse voltages.
(6)   Shielded Layer: Used up to 132 kV in star connected windings with graded insulation. Comprises of a number of concentric spiral coils arranged in layers grading the layers. The longest at the Neutral and the shortest at the Line Terminal. The layers are separated by cooling ducts. This type of construction ensures uniform distributed voltages.


Distribution transformers:

Distribution Transformers are normally Three Phase. These are generally rated at 11kv on the HV side and 415/433volts on the LV side. Some Distribution Transformers are rated at 33kv on HV side and 415/433 volts on LV side. The normal Ratings of the Distribution Transformers are: 25, 50, 75,100, 250,315,500,630 & 1000kva.The Standard Frequency of operation in India is 50Hz.

The Types of Distribution Transformers are:

(1)                       Conventional Non CSP

(2)                       Conventional CSP

(3)                       Sealed Non CSP

(4)                       Sealed CSP

(5)                       Hermetically sealed.

All the above types of Transformers are Oil Filled. The Core could be made of CRGO or Amorphous. Amorphous core provides low No Load Losses, No Load Current, Low Eddy Current Losses; the Core can be very thin, suitable up to Flux Density of 1.58T against 1.92T of CRGO.The Insulation materials used are Press Board, Kraft Paper, and Perma wood and Mineral Oil. The Winding Material is Copper, or Aluminum.

The cooling is generally natural. The cooling is done by one or more layers of Tubes, or Pressed Steel Radiators, or Corrugated Fins. The Transformers are suitable for Structural Mounting, Plinth Mounting (or Pad Mounted).

High voltage single phase distribution transformers:

These are generally connected between Phases on HV side and between phase and Neutral on LV side. These have the advantage of: Reducing Isq.R Loss, and Lines, prevent Failures of Transformers, provide quality supply, and prevent unauthorized Energy usage, Low Maintenance, and Easy to mount. Normally Stacked, CORE type construction with Mitred joint is used. Shell type core can also be used. The Core can be AMORPHOUS Metal or CRGO.

The conductor of the winding could be DPC or SE Aluminum or Copper. The transformer can have a LT MCCB and a HV Fuse Link and LA on HV side for Protection. The Transformer Tank could be Round, Elliptical or Rectangular but generally round. The Transformer is suitable for Pole Mounting or Plinth Mounting.

After Extensive cleaning, the Tank is sprayed with Powder Coated Paint which is extremely Hard, Scratch Free and Glossy. These Transformers when used for Agricultural Pump sets in Rural areas can ensure Quality, Trouble Free, Reliable, Dedicated Power supply to the consumer and protect him from the Adverse Effects of unauthorized Tapping of supply.

Dry Type Resin Cast Transformers:

These are Transformers, in which the insulating medium is Gas or Dry compound without insulating oil. These can be single phase or three phase, ventilated or non- ventilated, sealed with primary voltage greater than 600 volts. These have special applications. 

Amorphous metal transformers:

The use of Amorphous Metal Core instead of Silicone sheet steel reduces the No Load Losses by about 80%. A proprietary molten alloy of Iron, Boron, and Silicone is cooled rapidly at a rate of one million degrees centigrade per second such that Crystals are not formed. The Metal can be drawn very thin (0.025mm) and so exhibits very low eddy current loss. It is non-crystalline and it has a random molecular structure.

When AC Magnetic field is applied, the random atomic structure causes less friction and hence lesser Hysterisis Loss. However, it has a Low Space Factor of 80% as compared to 96% in respect of CRGO. Space Factor is defined as the Ratio of Core Cross sectional Area to the Area available for the Core, which means the weight, and cost (by about 30%) is more. The high initial cost however is compensated by the Lower No Load Losses which is advantageous when the Total Owning Cost over the life period of the Transformer is considered. This advantage helps in efficient use of available generation, better Demand side Management, Low Noise level, Lesser Temperature rise, reduction in Emissions at generating stations, etc.

Completely Self Protected (CSP) Transformers:

These transformers have primary protective fuse mounted inside the HV Bushings. A circuit breaker is provided immersed in the oil in the Tank for LV protection. This LT Circuit breaker trips for over loads and alerts the operator against over loads. The loads can be reduced and the CB taken back into service. However, it allows the CB to be closed in emergency by means of the external control for emergency restoration. It limits the temperature to 110 degrees Centigrade.

An external indication gives a warning of over load. A surge arrestor provided on the HV Bushings protects the Transformer against external surges. The Top cover of the Transformer Tank is welded. This transformer requires less maintenance and does not allow outsiders to meddle with.


Power Transformers:

The     Basic Material used in the construction of the Transformer are:
(1)               Structural Steel
(2)               Silicon Steel
(3)               Hard Drawn copper/Aluminum conductor
(4)               Solid Insulation
(5)               Insulating Oil

The Limits of Temperature rise as per IS 2026 (Part2):

(1)   Maximum Ambient Temperature:                                 --- 500C

(2)  Maximum Daily Average Air Temperature:                  --- 400C

(3)   Max. Yearly weighted average Air Temp:                    --- 320C

(4)   Minimum Ambient Air Temperature:                           --- 050C

For Water Cooled Transformers, the Maximum Temperature of cooling water should not be more than 30C and the average daily temperature should not be more than 250C As long as the Hot Spot Temperature based on Maximum yearly weighted average temperature is within 980C, the Transformer can have an expected life of 25 years. The Normal Vector Groups are: Yd1, Yd11, Yyo, Dy11, Dd0, Dy1, and Dzo. Depending on the application, the following other vector groups are also being used: Dz10,Yz11,Dd4,Dz4,Yz1,Dy5,Dd2,Dz2,Yd5,Yz5,Yd7,Dz0,Dd6,Dd8,Dz6,Dd10,Dy7,Yy 6,Yz7.

 

Accessories & Fittings:

The Transformers have the following Accessories & Fittings:

(1)       The HV & LV Bushings

(2)       Neutral and Body Earthing Terminals

(3)       Tank and its Lifting Lugs

(4)       Top Cover with its Lifting Lugs

(5)       Drain, Sampling and Filling Valves.

(6)       Oil Level Gauge

(7)       Explosion Vent Diaphragm

(8)       Silica Gel Breather


(9)       Off Circuit Tap Changer

(10)   Conservator Tank

(11)   Thermometer Pocket

(12)   Base Channels for Mounting.

The Vector Group of the Three Phase Transformer is generally Dy11.

Bushing: A structure carrying one or several conductors through a partition such as a wall or tank, and insulating it or them there from, incorporating the means of attachment (flange or other fixing device) to the partition. The conductor may form an integral part of the bushing or be drawn through.

Liquid Filled Bushing — A bushing in which the space between the inside surface of the insulating envelope and the solid major insulation is filled with oil or another insulating liquid.

Liquid Insulated Bushing — A bushing in which the major insulation consists of oil or another insulating liquid.


 Gas Filled Bushing — A bushing in which the space between the inside surface of the insulating envelope and the solid major insulation is filled with gas (other than ambient air) at atmospheric or higher pressure.

The definition includes bushings which are intended to form an integral part of gas insulated equipment, the gas of the equipment being in communication with that of the bushing.

Gas Insulated Bushing — A bushing in which the major insulation consists of gas (other than ambient air) at atmospheric or higher pressure.

NOTE:

1.   This definition includes bushings which are intended to form an integral part of gas insulated equipment, the gas of the equipment being in communication with that of the bushing.


2.    A bushing which contains solid insulating materials other than the envelope containing the gas (for example, support for conducting layers or insulating cylinder) is a composite bushing.

 Oil Impregnated Paper Bushing — A bushing in which the major insulation consists of a core wound from untreated paper and subsequently impregnated with an insulating liquid, generally the transformer oil. The core is contained in an insulating envelope; the space between the core and the insulating envelope being filled with the same insulating liquid as that used for impregnation.

Resin Bonded Paper Bushing — A bushing in which the major insulation consists of a core wound from resin coated paper. During the winding process, each paper layer is bonded to the previous layer by its resin coating and the bonding is achieved by curing the resin.

NOTE: A resin bonded paper bushing may be provided with an insulating envelope, in which case the intervening space may be filled with an insulating liquid or another Insulating medium.

 Resin Impregnated Paper Bushing — A bushing in which the major insulation consists of a core wound from untreated paper and subsequently impregnated with a curable resin.

NOTE: A resin impregnated paper bushing may be provided with an insulating Envelope, in which case the intervening space may be filled with an insulating liquid or another insulating medium.

Ceramic, Glass or Analogous Inorganic Material Bushing —A bushing in which the major insulation consists of a ceramic, glass or analogous inorganic material.

Cast Resin Insulated Bushing — A bushing in which the major insulation consists of a cast organic material with or without an inorganic filler.

Composite Bushing — A bushing in which the major insulation consists of a combination of different insulating materials.

 Capacitance Graded Bushing — A bushing in which metallic or non- metallic conducting layers are arranged within the insulating material for the purpose of controlling the distribution of the electric field of the bushing.


NOTE:

1.     Generally, the major insulation of a capacitance graded bushing is constituted of one of the following:

a)  Oil impregnated paper,

b)  Resin bonded paper,

c)  Resin impregnated paper,

d)  Cast resin,

e)  Gas or other insulating fluid, and

f)  Composite.

2.      A capacitance graded bushing may be provided with an insulating envelope, in which case the intervening space may be Indoor Bushing — A bushing, both ends of which are intended to be in ambient air but not exposed to external atmospheric conditions.

NOTE:

1.   In indoor installations, moisture condensation on the surface of the bushing is to be prevented, if necessary by ventilation or heating.

2.    This definition includes bushings operating in air at temperatures above ambient, such as occurs with air-insulated ducting.

Outdoor Bushing — A bushing, both ends of which are intended to be in ambient air and exposed to external atmospheric conditions.

Outdoor-Indoor Bushing — A bushing, both ends of which are intended to be in ambient air. One end is intended to be exposed to external atmospheric conditions and the other end is intended not to be so exposed

Indoor-Immersed Bushing — A bushing, one end of which is intended to be in ambient air but not exposed to external atmospheric conditions and the other end to be immersed in an insulating medium other than ambient air (for example, oil or gas)

Outdoor-Immersed Bushing — A bushing, one end of which is intended to be in ambient air and exposed to external atmospheric conditions and the other end to be immersed in an insulating medium other than air (for example, oil or gas).


Completely Immersed Bushing — A bushing both ends of which are intended to be immersed in insulating media other than ambient air (for example, oil or gas).

 

Earthing:

The Core of the Transformer is clamped to a Frame, which is in turn connected to the Tank. The Transformer is provided with two separate Earthing Terminal connections. These must be connected to two distinct Earthing Electrodes in the Substation. The Earth Resistance of these Electrodes must be less than 0.5 ohms. The Combined earth resistance shall be less than 0.1 ohm.

For Distribution Transformers, normally Dy11 vector Group, the LT Neutral is earthed by a separate Conductor section of at least half the section of the conductor used for phase wire and connected to a Separate Earth whose Earth Resistance must be less than 1 ohm. The Body of the Tank has two different earth connections, which should be connected to two distinct earth electrodes by GI flat of suitable section.

For Large Power Transformers, Neutral and Body Connections are made separately but all the Earth Pits are connected in parallel so that the combined Earth Resistance is always maintained below 0.1 ohm. The individual and combined earth resistance is measured periodically and the Earth Pits maintained regularly and electrodes replaced if required.

3.7.3  Lifting Lugs:   Two or Four Lifting Lugs are provided depending upon the size of the weight / size, for lifting the Transformer. The core also similarly provided with two or Four Lifting Lugs.

3.7.4   Drain, Sampling and Filling Valves:-There are two different types of Valves. (1) Wheel Valve (2) Butterfly Valve. The Wheel Valves are generally made of Cast Iron or gunmetal. These are used as Bottom Drain/Filter Valve, Top Filter Valve, and Isolating Valve between the Main Tank and the Conservator. The Butterfly Valves are used between the Main tank and the Radiators.

3.7.5    Off Circuit Tap Changer: These are provided on the side of the Transformer. These have to be operated only when the Transformer is de-energized. This can be manually operated with a Cranking Handle. A Lock is provided to lock the Tap Changer


in any Tap Position but not at any intermediate position. Interlocks can also be provided to trip off the Transformer if this mechanism is meddled when the Transformer is energised.

3.7.6   Ratio Changing Links: Some times, a Transformer will be required to function as a Common Standby for two different Power Transformers with separate LV voltages like 11 kV and 33kv. It is possible, for instance to manufacture and use a Power Trasformer with two different Ratios like 132/33-11kv.This Transformer can be used as 132/33 or 132/11 kv by changing the Ratio Changing the Links.

For changing the Links, the Transformer has to be de-enrgised; oil has to be drained below the inspection cover for the Links. After changing the Ratio by the Links, the Ratio has to be tested before taking back the unit into service.

On Load Tap Changer:

The Tap Changer has a Motor Drive Mechanism. The Motor rotes in the clockwise or anti clock wise direction when the taps raised or lowered either manually or electrically. The Tap changer operation is Step by Step. Limit switches provided cut off the OLTC at the End Taps. The Total operation by Motor takes about 40 to 70 milli seconds. A Bank Of Energy Storing Springs are provided , whose stored energy will be released for a very fast completion of Tap changing operation even when the drive motor supply is interrupted. In some cases the Transformer will be isolated if the Tap is stuck in an intermediate position.

The OLTC can be in One Compartment for 33kv Transformers and in two compartments to provide the selector Switch inside the Main tank and the Diverter outside the Main Tank. Make before Break switches, and Transition Resistors are provided in Diverter. The OLTC can be of a three phase Type or three Single-phase type. A separate Bucholtz relay or surge relays are provided to take care of any faults inside the OLTC gear. A separate Conservator Tank is provided for 33kv Transformers where as the Main Conservator Tank is partitioned for OLTC in large Power Transformers. The Contacts, Oil in divertor have to be maintained periodically for good performance.

3.7.8     Conservator Tank: This takes care of volumetric expansions of Oil in the Transformer. Its capacity is about 5% of the Main Tank. The Pipe from the Main Tank projects about 3 cm above the bottom of the Conservator Tank to collect sludge/moisture.


The Oil level in the Main Conservator is indicated by a Magnetic Oil Level Indicator which has also provision for Low Oil Level alarm or Trip. Generally the OLTC conservator has a prismatic oil level indicator.

A Silica Gel Breather is also provided for each of the Conservator Tanks. In case of large Power Transformers, a synthetic rubber made expansion bellow Barrier or a Diaphragm Barrier is provided to which the Breather is connected. This arrangement eliminates the contact of Transformer oil with Air.

 

Parallel Operation:

The condition required for paralleling two Transformers is:
(1)               Same Polarity
(2)               Same Voltage Ratio
(3)               Same Percentage Impedance.
(4)               Same Vector Group
(5)               Same Phase sequence.

 

Protection (Internal and External) of Transformer:
Internal protection:

a.      Bucholtz Relay: This Gas operated relay is a protection for minor and major faults that may develop inside a Transformer and produce Gases. This relay is located in between the conservator tank and the Main Transformer tank in the pie line which is mounted at an inclination of 3 to 7 degrees. A shut off valve is located in between the Bucholtz relay and the Conservator. The relay comprises of a cast housing which contains two pivoted Buckets counter balanced weights. The relay also contains two mercury switches which will send alarm or trip signal to the breakers controlling the Transformer.
In healthy condition, this relay will be full of oil and the buckets will also be full of oil and is counter balanced by the weights. In the event of a fault inside the transformer, the gases flow up to the conservator via the relay and push the oil in the relay down. Once the oil level falls below the bottom level of the buckets, the bucket due to the weight of oil inside tilts and closes the mercury switch and causes the Alarm or trip to be actuated and isolate the transformer from the system.
b.      Oil Surge/ Bucholtz Relay for OLTC: This relay operating on gas produced slowly or in a surge due to faults inside the Diverter Switch of OLTC protects the Transformer and isolates it from the system.
c.       Pressure Relief Valve for Large Transformers: In case of a serious fault inside the Transformer, Gas is rapidly produced. This gaseous pressure must be relieved immediately otherwise it will damage the Tank and cause damage to neighboring equipment. This relay is mounted on the top cover or on the side walls of the Transformer. The valve has a corresponding port which will be sealed by a stain less steel diaphragm .The diaphragm rests on a O ring and is kept pressed by two heavy springs. If a high pressure is developed inside, this diaphragm lifts up and releases the excessive gas. The movement of the diaphragm lifts the spring and causes a micro switch to close its contacts to give a trip signal to the HV and LV circuit breakers and isolate the transformer. A visual indication can also be seen on the top of the relay. For smaller capacity transformer, an Explosion vent is used to relieve the excess pressure but it can not isolate the Transformer.
d.      Explosion Vent Low & Medium Transformers: For smaller capacity Transformers, the excessive pressures inside a Transformer due to major faults inside the transformer can be relieved by Explosion vents. But this cannot isolate the Transformer.
e.       Winding/Oil Temperature Protection: These precision instruments operate on the principle of liquid expansion. These record the hour to hour temperatures and also record the Maximum temperature over a period of time by a reset table pointer. These in conjunction with mercury switches provide signals for excessive temperature alarm
annunciation and also isolate the Transformer for very excessive temperatures. These also switch on the cooler fans and cooler pumps if the temperature exceeds the set values. Normally two separate instruments are used for oil and winding temperatures. In some cases additional instruments are provided separately for HV, LV and Tertiary winding temperatures. The indicator is provided with a sensing bulb placed in an oil pocket located on the top cover of the Transformer tank. The Bulb is connected to the instrument housing by means of flexible connecting tubes consisting of two capillary tubes. One capillary tube is connected to an operating Bellow in the instrument. The other is connected to a compensating Bellow .The tube follows the same path as the one with the Bulb but the other end; it does not end in a Bulb and left sealed. This compensates for variations in Ambient Temperatures. As the temperature varies, the volume of the liquid in the operating system also varies and operates the operating Bellows transmitting its movements to the pointer and also the switching disc. This disc is mounted with mercury float switches which when made provides signals to alarm/trip/cooler controls. Oil and winding temperature indicators work on the same principles except that the WTI is provided with an additional bellows heating element. This heating element is fed by a current transformer with a current proportional to the load in the winding whose temperature is to be measured/monitored. The temperature increase of the heating element is proportional to the temperature rise of winding over top oil temperature. The operating bellow gets an additional movement simulating the increase of winding temperature over top oil temperature and represents the Winding Hot Spot. This is called Thermal Imaging process.
f.        Conservator Magnetic Oil Level Protection: Inside the conservator tank, a float is used to sense the levels of oil and move. This is transmitted to a switch mechanism by means of magnetic coupling. The Float and the Magnetic mechanism are totally sealed. The pointer connected to the magnetic mechanism moves indicating the correct oil level and also provision is made for Low oil level alarm by switch.
g.      Silica gel Breather: This is a means to preserve the dielectric strength of insulating oil and prevent absorption of moisture, dust etc. The breather is connected to the Main conservator tank. It is provided with an Oil seal. The breathed in air is
passed through the oil seal to retain moisture before the air passes through the silica gel crystals which absorbs moisture before breathing into the conservator tank. In latest large transformers, Rubber Diaphragm or Air cells are used to reduce contamination of oil.


External protection:

(1)                   Lightning Arrestors on HV & LV for Surge Protection

(2)                   HV / LV Over Current Protection(Instantaneous /IDMT- Back up)

(3)                   Earth Fault Protection (Y connected side)

(4)                   REF (HV & LV) ( For internal fault protection)

(5)                   Differential Protection (for internal fault protection)

(6)                   Over Fluxing Protection (against system Kv & HZ variations)

(7)                   HG Fuse Protection for Small Capacity Transformers.

Normally Each Power Transformers will have a LV Circuit Breaker. For a Group of Transformers up to 5 MVA in a substation, a Group control Circuit Breaker is provided. Each Transformer of 8 MVA and above will have a Circuit Breaker on the HV side.

 

Drying of Transformers:

Distribution Transformers: These are thoroughly dried at the Factory and filled with New Filtered and Tested Transformer Oil before dispatch. When it is received at site, the IR values and the Oil Tests (Dielectric and Acidity) are checked. If OK, the Transformer can be commissioned if all the pre-commissioning Tests are satisfactory.

Power Transformers: These are also thoroughly dried at the Factory before dispatch. However, large Transformers are sent without oil with Conservator, Radiators, Bushings, Protective devices etc packed separately and the Transformer filled with Nitrogen. All the Manholes, etc is blanked off. Under such circumstances, the drying out in the field will take very less time.

The real drying is not so much for the Oil but for the winding, which might have absorbed moisture. Vacuuming, and oil Filtration is necessary and the process may take more than a month. The criteria to determine that the drying out is completed are the


 

 245 kV Power transformers:

 

(a) Two winding

Three phase rating

MVA

Voltage ratio

Impedance voltage

(percent)

Cooling

50

220/66 kV

12.5

ONAN/OFAF (or)

ONAN/ODAF

100

220/66 kV

12.5

ONAN/OFAF (or)

ONAN/ODAF

100

220/33 kV

15.0

ONAN/OFAF (or)

ONAN/ODAF

(b)Inter Connecting Auto Transformers

35,50

220/33

10

ONAN/OFAF

50

220/132

10

ONAN/OFAF

100

220/132

12.5

ONAN/ONAF/OFAF

(or) ONAN/ONAF/ODAF

160

220/132

12.5

ONAN/ONAF/OFAF

(or) ONAN/ONAF/ODAF

200

220/132

12.5

ONAN/ONAF/OFAF

(or) ONAN/ONAF/ODAF


 

Auto Transformers(420 Kv Level)Constant Percentage Impedance:

 

Three-phase HV/IV/LV

Voltage ratio

Tapping range per

cent

 

Per cent impedance voltage

 

Cooling

MVA

 

 

HV-IV

HV-LV

IV-LV

 

 

100/100/33.3

 

400/132/33

+10% to -

10% 16 steps

of 1.25%

 

12.5

 

27

 

12

 

ONAN/ONAF

 

200/200/66.7

 

400/132/33

+10% to -

10% 16 steps

of 1.25%

 

12.5

 

36

 

22

ONAN/ONAF

or ONAN/ONAF

 

2580/250/83.3

 

400/220/33

+10% to -

10% 16 steps

of 1.25%

 

12.5

 

45

 

30

ONAN/ONAF

or ONAN/ONAF


 

315/315/105

 

400/220/33

+10% to -

10% 16 steps

of 1.25%

 

12.5

 

45

 

30

ONAN/ONAF

or ONAN/ONAF

 

500/500/166.7

 

400/220/33

+10% to -

10% 16 steps

of 1.25%

 

12.5

 

45

 

30

ONAN/ONAF

or ONAN/ONAF

 

630/630/210

 

400/220/33

+10% to -

10% 16 steps

of 1.25%

 

12.5

 

45

 

30

ONAN/ONAF

or ONAN/ONAF

 

Auto transformers (800 kV level):- 

 

 

Three phase rating HV/IV/LV MVA

 

Voltage ratio KV

 

Tapping range(percent)

 

Percent impedance voltage

 

 

Cooling

 

HV-IV

HV-

LV- IV-LV

 

 

315/315/105

 

765/220/33

+4.5%

-7.5%

24 steps

 

12.5

 

40

 

25

ONAN/ONAF

or ONAN/ODAF

or ODAF

630/630/210

765/400/33

-do-

12.5

60

40

-do-

750/750/250

-do-

-do-

-do-

-do-

-do-

-do-

1000/1000/333.3

-do-

-do-

14

65

45

-do-

 

1500/1500/500

 

-do-

 

-do-

-do- tolerance

-do-

+10%

-do-

+ 15%

 

+ 15%


SAMPLE CHECK LIST IN TRANSFORMER ERECTION:

 

1.      Testing of Oil samples for BDV in Main Tank and OLTC.

2.      Oil level in Main Conservator and OLTC Conservator

3.      Capacitance and Tan Delta values of all the HV Bushings

4.      Oil level in HV Bushings

5.      Cleanliness of Bushings and Tightness of connections

6.      Tightness of Bushing Test tap plugs

7.      Locking in of Main/ OLTC Bucholtz relays released

8.      Locking in of MOG is released

9.      Test switch of Bucholtz relay kept in S (service) position

10.  All the Radiator valves (Top & Bottom) Opening ensured

11.  Release air from Bushings and close the valve

12.  Release air fro the Bucholtz relays and close

13.  Test Bucholtz relay for proper operation by air injection

14.  Shut off valve of Main/OLC Bucholtz/Surge relays are opened

15.  Oil seal is ensured for the Breather

16.  Silica gel for the Breather is Blue in color

17.  All Radiator Top and Bottom valves are opened

18.  All Filter/ sampling/ drain valves are properly closed

19.  Main/OLTC Conservator Oil filling caps are tight.

20.  Oil filling in OTI and WTI pockets/ Calibration of WTI/OTI

21.  No oil leaks any where

22.  Explosion vent diaphragm top and bottom are in place

23.  Release air from top cover

24.  Tank Double point earth and connected to two different earths

25.  Earth Resistance of Earth pits

26.  HV/ LV neutrals are earthed

27.  Bi directional Rollers are locked

28.  Alarm and indications and trip connections ensured after operating the concerned relays

Comments